Solar Distribution Box DC+AC 2 String 3PH SPD T2 - B16 SPD T2 RCD 40A 100mA
SKU
3146
Solar Distribution Box DC+AC 2 String 3PH SPD T2 - B16 SPD T2 RCD 40A 100mA is available to buy in increments of 1
Junction box (GARD. TYPE 2, 2 MPPT // GARD. TYPE 2 16A 3F, RCD 100mA)
- The boxes are designed for use in two-string photovoltaic installations with or without an isolated lightning protection system.
- AC side three-phase. Their design is suitable for surface mounting, ready for connection.
- DC and AC protection in a single housing.
Features:
- 2 x module chains
- 2 x DC type 2 surge arrester
- 1 x type 2 AC surge arrester
- 1 x 3-phase overcurrent circuit breaker 16A
- 1 x residual current circuit breaker 100mA
- MC4 board connections
- Degree of protection IP65
- Transparent door
- Protection class II
- Colour: white
ELECTRICAL AND MECHANICAL PARAMETERS OF THE ENCLOSURE:
- Manufacturer: Noark
- Model: PHS 24T
- Number of modules: 24
- Design in accordance with standards: EN 60670-1, EN 62208
- Degree of protection: IP65
- Protection class: II
- Rated insulation voltage (Ui): 690 V AC, 1000 V DC
- Glow rod test: 650°C
- Impact resistance: IK08
- Recyclable plastic: halogen-free
DC SURGE ARRESTER USED:
- Manufacturer / Model: PHOENIX / VAL-MS 1000DC-PV/2+V
- Surge protection: Type 2
- Maximum permanent voltage UCPV: 1170 V DC
- Short-circuit resistance I SCPV: 2000 A
- Long-term operating current ICPV: <20 uA
- Rated load current IL: 80 A
- Protective conductor current IPE: <=20 uA DC, <=250 uA AC
- Standby power consumption PC: <=25 mVA
- Rated dissipated current (8/20) us: 15 kA
- Maximum discharge current Imax (8/20) us: 40 kA
- Total discharge current Itotal (8/20) us: 40 kA
- Protection level Up: <= 3.7 kV
- Residual voltage Ures:
- <= 3.7 kV (at In)
- <= 3.1 kV (at 5kA)
- <= 3.5 kV (at 10kA)
- <= 4 kV (at 20kA)
- <= 4,6 kV (at 30kA)
- <= 5 kV (at 40kA)
- Response time tA: <= 25ns
- Riso insulation resistance: <= 5 Giga OM (at 500 VDC)
AC SURGE ARRESTER USED:
- Manufacturer: Noark
- Model: Ex9UE2 12.5 3PN 275
- Design in accordance with: EN 61643-11
- Arrester type: Type 2 (Class II, C, T2)
- Insertion type: L-N: MOV (varistor), N-PE: GDT (spark gap)
- Endurance voltage Uc: L-N: 275 V AC, N-PE: 255 V AC
- Frequency f: 50-60Hz
- Rated discharge current In (8/20 us): L-N: 20 kA per pole, N-PE: 40 kA per pole
- Max. impulse current limp (10/350 us): N-PE: 12 kA per pole
- Max. discharge current Imax (8/20 us): 40 kA per pole
- Voltage protection level Up for current In: L-N: 1,4 kV, N-PE: 1.5 kV
- Voltage protection level Up for current Imax: L-N: 2 kV, N-PE: 1.5 kV
- Voltage protection level Up for 5 kA (8/20 us): L-N: 2 kV, N-PE: 1.5 kV
- N-PR follow-up current suppression capacity Ifi: 100A
- Surge current Ut (withstand): L-N: 5s : 335 V, N-PE: 200 ms : 1200 V
- Arrester voltage for 1mA current: 387 -
Manufacturer | Zineric |
---|---|
Weight | 3.850000 |
Warranty | 5 |
Voltage | AC+DC |
Number of Phase | 3-phase |
Circuit Protection | 2 |
SPD Types | T2 |