Zineric ZIN-BOX Solar Distribution Box AC 13-15kW 3PH B32 SPD T2
SKU
3134
Zineric ZIN-BOX Solar Distribution Box AC 13-15kW 3PH B32 SPD T2 is available to buy in increments of 1
Complete Zineric Photovoltaic AC Switchgear for self-assembly:
Characteristics:
- 1 x type 2 AC surge arrester
- 1 x 3-phase overcurrent circuit breaker 32A
- Ready to connect.
- Modular design
- Degree of protection IP65
- Transparent door
- Protection class II
- Colour: white
Specification:
- AC side three-phase.
- Their design is suitable for surface mounting, ready for connection.
Switchgear suitable for photovoltaic installations in the 13-15kW power range
Attention:
For ease of product navigation, it has been suggested to select the modular apparatus on the AC side under the inverter power and on the DC side under the number of MPPT.
However, in order to select the correct switchgear, the inverter data sheet should be read in detail and the appropriate Zineric switchgear should be selected by a qualified electrician.
ELECTRICAL AND MECHANICAL SPECIFICATIONS OF THE ENCLOSURE
- Model PHS 8T
- Number of modules 8
- Design in accordance with EN 60670-1, EN 62208
- Degree of protection IP65
- Protection class II
- Rated insulation voltage (Ui) 690 V AC, 1000 V DC
- 650°C glow rod test
- Impact resistance IK08
- Halogen-free recyclable plastic
B32 3F OVERCURRENT CIRCUIT BREAKER USED
- Manufacturer/model Noark/Ex9BN 3P B32
- Rated current 32A; 3-phase
- Number of poles 3
- Characteristic B
- Version according to IEC/EN 60898-1
- Rated short-circuit breaking capacity ICN 6kA
AC T2 SURGE ARRESTER USED
- Manufacturer/model Noark/Ex9UE2 12.5 3PN 275
- Design in accordance with EN 61643-11
- Arrester type Type 2 (Class II, C, T2)
- Insertion type L-N: MOV (varistor), N-PE: GDT (spark gap)
- Endurance voltage Uc L-N: 275 V AC, N-PE: 255 V AC
- Frequency f 50-60Hz
- Rated discharge current In (8/20 us) L-N: 20 kA per pole, N-PE: 40 kA per pole
- Max. Impulse current limp (10/350 us) N-PE: 12 kA per pole
- Max. Discharge current Imax (8/20 us) 40 kA per pole
- Voltage protection level Up for current In L-N: 1,4 kV, N-PE: 1.5 kV
- Voltage protection level Up for current Imax L-N: 2 kV, N-PE: 1.5 kV
- Voltage protection level Up for 5 kA (8/20 us) L-N: 2 kV, N-PE: 1.5 kV
- N-PR fault current suppression capability Ifi 100A
- Surge surges Ut (withstand) L-N: 5s : 335 V, N-PE: 200 ms : 1200 V
- 1 mA arrester voltage 387 - 473 V
- Maximum fuse rating L-N: max. 125 A gG, N-PE: -
- Short-circuit current withstand capability L-N: 50 kA, N-PE: -
EAN | 5906639360025 |
---|---|
Manufacturer | Zineric |
Weight | 2.600000 |
Warranty | 5 |
Inverter Min Power | 13 |
Inverter Max Power | 15 |
Voltage | AC |
Number of Phase | 3-phase |
SPD Types | T2 |
Width In Number Of Modular Spacings | 12.00 |
IP Code | IP65 |
Colour | White |