Characteristics:

  • The PR8NM type A/AC residual current circuit breaker, commonly known as a differential, circuit breaker or residual current circuit breaker (abbreviated RCD or RCCB), is an electrical protective devicea protective device that disconnects an electrical circuit when it detects that the current flowing out of the circuit is not compatible with the incoming current.
  • Its main purpose is to protect people from electric shock, both in the case of indirect and direct contact.
  • In addition, it limits the effects of damage to electrical equipment and minimises the risk of fire.
  • Residual current circuit breakers are used both in residential buildings and in industry.
  • The PR8NM line of Type A/AC residual current circuit breakers, also known as Type A/AC circuit breakers, are used in electrical circuits supplied with a current offrequency of 50/60 Hz and rated voltage of 230 V (for two-pole circuit breakers) or 400 V (for four-pole circuit breakers) and rated current of 25 A to 63 A.
  • They comply with the IEC/EN 61008-1 standard.
  • Assembly of the circuit breakers is only possible by qualified personnel. It is recommended to disconnect the power supply before mounting.
  • The switches can be easily mounted on a TH35 rail using plastic mounting clips.
  • The device is equipped with an easy-to-read operation indicator to improve safety in use.
  • The PR8NM type A/AC line residual current circuit breakers have a TEST button for regular verification of the correct internal operation of the device and should be activated every 30 days.

Technical data:

  • Type: AC
  • Rated current: 63 A
  • Rated residual current A: 100 mA
  • Rated residual current switching capacity A: 500
  • Tripping time: 0.1 s
  • Resistance to voltage shock Uimp: 6000 V
  • Short-circuit resistance Inc: 6000
  • Pollution degree: 2
  • Rated voltage Ue: 400 V
  • Rated insulation Ui: 500 V
  • Current frequency: 50/60 Hz
  • Electrical life: 4000
  • Mechanical life: 4000
  • Operating position indicator: Yes
  • Degree of protection: IP 20
  • Storage temperature: -30/+70°C
  • Operating temperature: -30/+50°C
  • Maximum cross-section of connecting wires: 25 mm²
  • Tightening torque of connection terminals: 3 Nm
  • Possibility of connection via comb rails: Yes
More Information
ManufacturerVCX
Weight0.380000
Warranty2
VoltageAC
Number of Phase3-phase
Width In Number Of Modular Spacings4.00
IP CodeIP20
Width10.00 cm
Height8.00 cm
Length/Depth8.00 cm
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
More from VCX
  1. VCX SPD DC 1200V 3P T2
    VCX SPD DC 1200V 3P T2
  2. VCX C4P SPD AC 3PH 4P T2
    VCX C4P SPD AC 3PH 4P T2
  3. VCX SPD DC 1000V 2P T2
    VCX SPD DC 1000V 2P T2
Copyright © 1992-present ecoABM sp. z o.o. All rights reserved.